| Technical Parameters | C3351-B01 |
| Programming Software | CODESYS V3.5.19.70 |
| Programming language | IEC 61131-3LD,IL,ST,CFC/FBD,SFC |
| Maximum State Tasks | 5 |
| Program Memory | 4M Bytes |
| Data Storage | 4M Bytes |
| Power-down Protection Area | 32K Bytes |
| General Parameters | |
| System power supply | 19.2-28.8VDC(Nominal 24VDC) |
| Protection | Anti-reverse connection protection |
| Module consumption | 70mA@24Vdc |
| Internal Bus supply current | Max:2.0A@5VDC |
| Isolation | system to site power isolation |
| Field power supply | 19.2-28.8V(Nominal 24V) |
| Field supply current | Max. DC 8A |
| Number of supported I/O modules | 32 pcs |
| Wiring diameter | Max.1.5mm² (AWG 16) |
| Way to install | 35mm DIN rail |
| Dimension | 115 * 65.5 * 75mm |
| Weight | 120g |
| Environment Specification | |
|
Operational Temperature
|
-30~70℃ |
|
Operational Humidity
|
5%~95% RH(No Condensation) |
| Ingress Protection Rating | IP20 |
| Profinet Parameter | |
| Programming Software | CODESYS SP17 |
| Programming language | IEC 61131-3 (LD, IL, ST, CFC/FBD, SFC) |
| Maximum State Tasks | 5 |
| Bit Instruction Cycle | 0.21us |
| Word Transfer Cycle | 0.39us |
| Floating Point Operation Cycle | 0.42us |
| Program Memory | 4MBytes |
| Data Storage | 4MBytes |
| Power-down Protection Area | 32KBytes |
| RTC: | Not Supported |
| Maximum Expansion Module | 32 |
| Modbus Master Max Channel Numbers | 10 |
| Function Code 1(Read Coils) | 2000 |
| Function Code 2(Read Discrete Inputs) | 2000 |
| Function Code 3(Read Holding Registers) | 125 |
| Function Code 4(Read Input Registers): | 125 |
| Function Code 15(Write Multiple Coils) | 440 |
| Function Code 16(Write Multiple Registers) | 27 |
| Function Code 23(Read/Write Multiple Registers) | 25+25 |
| Interface | 2 * RJ45 & 1 * RS485 |
| Network Port Baud Rate | 10/100Mbps, Adaptive and full duplex |
| Network Protocol | Modbus TCP,the default IP of the device is 192.168.0.15 |
| Serial Port Configuration(RS485) | Supports Modbus RTU/ASCII, the baud rate is 2400~115200bps, and supports the parameter configuration of parity code and stop bit |
| LED indicator | 6 LEDs PWR STAT RUN NET IRN IER |
| Modbus TCP Client | Max supports for connecting 6 Modbus TCP servers |
| Modbus TCP Server | Max supports for 6 Modbus TCP clients connected |
| Modbus RTU Master | Max supports for connecting 5 slave devices |
| Modbus RTU Slave | Max supports for connecting 1 master device |








If you are interested in the product, contact 2bvideo.com for more information for more information
The information of 2bvideo.com limited shown above is provided by the user or collected on the network. Video 2B does not guarantee the authenticity,accuracy and legitimacy of 2bvideo.com limited information. Video 2B does not involve legal relationships and disputes between users arising from transactions other than secured transactions on this website. Disputes shall be settled by you through negotiation. If you are the person in charge or relevant employee of this enterprise, if you find that the enterprise information is incorrect or want to manage thiscompany, please contact us jacklee1558@gmail.com, after you claim the enterprise, you can obtain management permission, publish supplyand demand information, bring consulting orders, and remove page advertisements.